Troubleshooting

Find your symptom, try the checks in order, and contact your partner if it isn't fixed. Have the details listed in Support and Warranty ready.

Stop first

Smoke, a burning smell, sparks, liquid inside, a part too hot to touch, or a PDU overload alarm: press and hold the PDU power button (or unplug if it's safe), don't restart, and contact your partner.

Power​

SymptomCheck
PDU display stays darkCord pushed in at both ends; the outlet works (try another device); breaker not tripped; extension cord, if any, works
PDU on, but nothing else startsPress and hold the PDU power button to switch the outlets on. Wait 60 seconds
Switch dark after 2 minutesCheck outlet 4 (NUC PRO) or 3 (HR-01-2) is on in the PDU display. Still dark: contact your partner
A node won't startIts outlet is on; its power cable is seated; press its power button once
Outlets switch off on their ownPossible overload. Check the PDU display, reduce load, disconnect accessories

Network and access​

SymptomCheck
Can't reach anythingLaptop cable in a free switch port; laptop IP settings match the method in First Network Access
Can't find a device's addressDHCP lease list on your gateway or site network; the PDU display shows the PDU's IP; your Access & Configuration Sheet
hiveradar-edc-<serial6>.local doesn't openThe network may block mDNS. Use HiveSight's IP or its 169.254 address from your sheet
Login refusedYou're using the right device's login from your sheet. Ask your partner if they changed it
HCI console doesn't loadNodes finished booting (3-5 minutes); right address; you continued past the certificate warning; no laptop firewall blocking 443
A node shows offline in the HCINode powered on; its cables and keystone seated (see Ports and Addresses); restart it from its PDU outlet if it hung
Gateway has no powerPort 8 to splitter PoE input, splitter data to Mako LAN 1, splitter DC to Mako DC port; switch powered
No internetGateway signal and SIM/APN, or site uplink on port 8

HiveSight​

SymptomCheck
HCI card says Unreachable or StaleCluster address and login in Settings; the HCI is up; for StorMagic, every node's IP is listed
EDC Devices card emptySwitch and PDU must be cloud managed and online. Standalone devices aren't shown yet
Update failsNeeds internet. HiveSight rolls back automatically; try again later
StorMagic witness downSBC powered (port 7 NUC PRO, port 3 HR-01-2); add-on on in Settings > Add-ons; nodes can reach TCP 4174
Forgot the HiveSight passwordAnother admin can reset it in User Management. There is no factory reset; contact your partner

Cooling​

SymptomCheck
Fans silentNormal below about 25 °C in the top drawer. If the unit is warm: top drawer pushed fully in (fans stop when it's pulled out)
Fans loud all the timeProfile switch on Turbo; warm room; heavy load; rear exhaust blocked
Temperature warnings or throttlingFront and rear clear; top drawer empty; room within 5-35 °C; switch to Turbo; dust (clean front to rear with compressed air, powered off)

Drawers, lighting and mast​

SymptomCheck
Drawer stuckBoth twist locks fully open; nothing caught behind it. Don't force it
Drawer LEDs offInterior lighting on (button on the logo plate); drawer not pulled out past its power point
Pole won't screw inRubber cover off; main pole's bottom section extended first
Pole sections won't slideTwist counter-clockwise to unlock first; clean dust off the joints
Equipment wobbles on the mastT-bar and orientation knob tight; load under 3 lb and centered; retract in wind